⚡️ Short answer first
The Sunsynk will never energise its “Grid / Gen-IN” terminals when it is running off-grid, so a Hoymiles (or any other grid-tied micro-inverter) that is plugged into those terminals will see no AC reference and will therefore sit there flashing red.
👉 Move the micro-inverter to a point that IS energised by the Sunsynk (usually the “LOAD / AC-OUT / UPS” bus) and switch on the built-in “AC-coupling” function in the menu.
That’s all that is really required.
Below is the long-form explanation plus the exact menu items (names vary slightly by firmware) and a wiring sketch.
1. Why it is not working now
- Off-grid mode = the Sunsynk produces 230 V/50 Hz only on its AC-OUT terminals.
- The “Grid / Gen-IN” connector is an input only; it is dead unless an external grid or generator is actually present.
- A Hoymiles needs a live grid to sync to; no grid → red LED → 0 W reported in the app.
So the fix is not really a software tweak; it is a wiring/parameter combination:
• Put the micro-inverter on the side that always has power (AC-OUT).
• Tell the inverter that there may be extra AC power coming in and what to do with it → “AC-Coupling = ON”.
2. Recommended wiring diagram
PV strings → PV1 / PV2 (DC) ──┐
Battery → BAT± ──┤ Same as today
Loads → AC-OUT (L/N/E) ──┤
Micro-PV → AC-OUT (L/N/E) ← move here
CT clamp → Around AC-OUT cable to loads (arrow → grid)
Grid / Gen → — (nothing connected while fully off-grid)
If your inverter has two separate AC-OUT terminals (UPS + LOAD) you can land the micro-inverter on either; they are internally common.
3. Key menu items (typical Sunsynk / Deye FW ≥V1.1xx)
Advanced menu (press & hold ENTER 5 s):
| # | Setting (name may differ) | Suggested value / comment |
|---|
| 71 | AC-Coupling Enable | ON (or “Allow AC charge”) |
| 72 | Max AC-Charge Power | = Hoymiles rating (e.g. 800 W) |
| 49 | AC-Charge Current Limit | Match 72 / battery spec |
| 25 | CT Function | Enable / “Meter” |
| 26 | CT Direction | Calibrate so EXPORT = 0 |
| 11 | Output Priority | SBU (Solar-Battery-UPS) or similar |
| 12 | Charge Source Priority | PV > AC |
| 35 | Grid-Tie / Off-grid mode | Off-Grid (that stays the same) |
Save / exit, then power-cycle the inverter once.
After boot the LCD / app should now show an extra line:
“AC-Couple Power” or “Gen-Power” = whatever the Hoymiles is making.
4. If you really want to use the GEN port
Some newer Sunsynk models have a dedicated GEN port that can be “self-excited” (Parameter 101: Gen Port Energise = ON).
That forces the inverter to push a tiny seed voltage onto the GEN pins so the micro-inverter can start.
Most installers still prefer the AC-OUT method because it is simpler and documented in Sunsynk’s own “AC-Coupled PV” application note.
5. Things to double-check
- Firmware ≥ V1.1.7: older FW throttled AC-PV poorly and would trip the micro-inverter.
- Battery must be able to absorb the extra power: set
Max Charge Current high enough.
- Correct CT orientation: get “Grid Export = 0 W” when battery full, load met.
- When batteries reach full and loads are low the Sunsynk will ramp PV down to keep voltage ≈ 230 V; if the micro-inverter still sees > 253 V it will shut itself off (normal).
6. Quick troubleshooting flow
- Move AC cable ⇒ AC-OUT.
- Turn on AC-Couple menu items ⇒ save / reboot.
- Wait 1–2 minutes: Hoymiles green LED should come on solid.
- LCD: look for “AC-Couple” power or watch in the Solarman / Sunsynk app.
- If still flashing red → measure AC voltage on that plug (should be 230 V ± 2%).
🎉 That’s it!
Once wired to AC-OUT with AC-Coupling enabled, the system will happily:
• Use DC-PV first,
• Top up any shortfall with the Hoymiles AC-PV,
• Charge the battery with any excess,
• Ramp everything down automatically when the battery is 100 %.
Let me know how it goes or if you need the exact parameter numbers for your particular firmware.