if frequency is changing not volatge how will the core iron loss vary?
- User
if frequency is changing not volatge how will the core iron loss vary?
- Assistant
Great question. Core (iron) loss = hysteresis loss + eddy-current loss, and they react differently when you change frequency while holding voltage constant.
- Flux density B ∝ V/f. So if V is fixed and f goes up, B goes down.
- Hysteresis loss: P_h ∝ f · B^α ≈ V^α · f^(1−α). With α ≈ 1.6–2.0, 1−α is negative, so P_h decreases as frequency increases (at constant V).
- Eddy-current loss: P_e ∝ f^2 · B^2 ≈ V^2 (roughly constant with frequency, for laminated cores in this range).
So, at constant voltage: P_core(f) = P_h(f) + P_e(f) ≈ A · f^(1−α) + B → As f increases, total core loss tends to drop toward the (roughly constant) eddy-current component; as f decreases, core loss rises. At sufficiently low f, the core can saturate (since B ∝ 1/f), and losses shoot up beyond these simple laws.
How to estimate numerically: If at 50 Hz the iron loss is P_fe1 and the hysteresis share is m (say 0.7) with α ≈ 1.6, then P_fe2 ≈ P_fe1 [ m · (f2/f1)^(1−α) + (1−m) ]. Example at same V: 2.5 kW at 50 Hz → at 60 Hz ≈ 2.5[0.7·(60/50)^(−0.6)+0.3] ≈ 2.32 kW.
If you want, tell me the new frequency and I’ll plug in numbers (and we can pick a reasonable hysteresis fraction for your core).