3.2 System Boot and iLO Verification 3.2.1 H1 Configuration Server Model: H1 HPE…
- User
3.2 System Boot and iLO Verification 3.2.1 H1 Configuration Server Model: H1 HPE ProLiant DL360 Gen11 Silver server Test Item Expected Result Result (OK/NOK) Comments Boot Verification Power On Self Test (POST) Completes without errors System Boot Can boot to BIOS/OS installer Error Messages No critical errors during POST iLO Access and License iLO Web Interface Accessible via dedicated port iLO Advanced License License activated Hardware Detection via iLO Processors 2x Intel Xeon-Silver 4410Y detected Processor Cores 24 total cores (2x12) Memory 128GB DDR5-4800 detected Storage Controller HPE MR416i-o with 8GB cache System Drives 2x 960GB SATA SSD detected Network Adapter Broadcom BCM5719 4-port detected Power Supplies 2x 800W PSUs online System Health via iLO Temperature Status All sensors within normal range Fan Status All fans operational Power Redundancy Both PSUs sharing load Storage Battery Smart Storage Energy Pack (Status: OK) Firmware and Driver Version Check BIOS Firmware iLO Firmware RAID Controller Firmware NIC Firmware
Serial Number Verification Table (H1 HPE ProLiant DL360 Gen11 Silver server):
Serial Number Post Boot iLO Access Hardware Detection System Health Overall SGHD2JJ7QY SGHD2JJ7R7 SGHD2JJ7RJ SGHD2JJ7RT SGHD2JJ7S3 SGHD2JJ7R1 SGHD2JJ7RB SGHD2JJ7RM SGHD2JJ7RX SGHD2JJ7S6 SGHD2JJ7R4 SGHD2JJ7RF SGHD2JJ7RQ SGHD2JJ7S0
Comment: network adapter: Please add item to check the other interface as specified in the tender document:
- at least one (1) GbE port (with RJ-45 connector) for out-of-band management
- at least one (1) VGA display ports for rack manager
- at least one (1) front USB 3.2 and two (2) rear USB 3.2 or above port power supplies: add hot swap test, remove one PSU, ensure the server continues running without iLo errors system health via iLO to add : execute insight diagnostics in iLO to assess CPU, memory, motherboard, fan test and storage controller health. Check any error codes from the diagnostics. fan status: to check at least seven redundant hot swappable fans
Assistant
I'll help you refine your server verification checklist. Based on your comments, here's an improved version that includes the additional checks:
3.2 System Boot and iLO Verification
3.2.1 H1 Configuration
Server Model: H1 HPE ProLiant DL360 Gen11 Silver server
Test Item Expected Result Result (OK/NOK) Comments Boot Verification Power On Self Test (POST) Completes without errors System Boot Can boot to BIOS/OS installer Error Messages No critical errors during POST iLO Access and License iLO Web Interface Accessible via dedicated port iLO Advanced License License activated Hardware Detection via iLO Processors 2x Intel Xeon-Silver 4410Y detected Processor Cores 24 total cores (2x12) Memory 128GB DDR5-4800 detected Storage Controller HPE MR416i-o with 8GB cache System Drives 2x 960GB SATA SSD detected Network Adapters Broadcom BCM5719 4-port detected Management Port 1x GbE port (RJ-45) for out-of-band management Display Ports At least 1x VGA port for rack manager USB Ports 1x front USB 3.2 and 2x rear USB 3.2 or above Power Supplies 2x 800W PSUs online System Health via iLO Temperature Status All sensors within normal range Fan Status All 7+ redundant hot-swappable fans operational Power Redundancy Both PSUs sharing load PSU Hot-Swap Test Server runs without errors when one PSU removed Storage Battery Smart Storage Energy Pack (Status: OK) iLO Diagnostics Insight Diagnostics executed with no errors for CPU, memory, motherboard, fans, and storage controller Firmware and Driver Version Check BIOS Firmware iLO Firmware RAID Controller Firmware NIC Firmware Serial Number Verification Table (H1 HPE ProLiant DL360 Gen11 Silver server):
Serial Number Post Boot iLO Access Hardware Detection System Health Overall SGHD2JJ7QY SGHD2JJ7R7 SGHD2JJ7RJ SGHD2JJ7RT SGHD2JJ7S3 SGHD2JJ7R1 SGHD2JJ7RB SGHD2JJ7RM SGHD2JJ7RX SGHD2JJ7S6 SGHD2JJ7R4 SGHD2JJ7RF SGHD2JJ7RQ SGHD2JJ7S0 I've added all the requested items:
- Additional interface checks (management port, VGA port, USB ports)
- PSU hot-swap test
- Expanded fan status check to specify 7+ redundant hot-swappable fans
- Added iLO Diagnostics check for comprehensive system health verification
Would you like me to make any additional modifications to this verification checklist?