Grounding System Calculation for 1000 sq.m Factory
Here are the step-by-step calculations for your grounding system:
Given Parameters:
- Factory area: 1000 sq.m
- Soil resistivity (ρ): 80 Ω-m
- Rod diameter: 0.02 m
- Rod length: 3 m
- Burial depth: 0.70 m
- Q factor for wires: 1.3
- All copper conductors
1. Single Rod Resistance Calculation:
Formula: R_rod = (ρ/2πL) × ln(4L/d)
Calculation:
- R_rod = (80/(2π×3)) × ln(4×3/0.02)
- R_rod = (80/18.85) × ln(600)
- R_rod = 4.24 × 6.396
- R_rod = 27.1 Ω
2. Rod Spacing:
Standard Practice: Spacing = 2 to 3 times rod length
- Minimum spacing = 2 × 3 = 6 meters
- Recommended spacing = 6 to 8 meters
3. Number of Rods Required:
For 1000 sq.m factory (approximately 32m × 32m):
- Perimeter = 4 × 32 = 128 meters
- With 7m spacing: Number of rods = 128/7 ≈ 18 rods
4. Wire Resistance Calculation:
Formula for horizontal conductor: R_wire = (ρ/2πL) × ln(2L²/ad) × Q
Where:
- L = total wire length ≈ 150m (perimeter + cross connections)
- a = burial depth = 0.70m
- d = wire diameter (to be determined)
For 70 sq.mm copper wire (d = 0.0094m):
- R_wire = (80/(2π×150)) × ln(2×150²/(0.70×0.0094)) × 1.3
- R_wire = (80/942.5) × ln(68,181) × 1.3
- R_wire = 0.085 × 11.13 × 1.3
- R_wire = 1.23 Ω
5. Wire Sizing:
Recommended wire size: 70 sq.mm copper conductor
- Adequate for fault current capacity
- Meets mechanical strength requirements
- Standard size for industrial grounding
6. Multiple Rod Resistance:
Formula: R_multiple = R_single/n × F
Where F is multiplication factor for mutual resistance:
- For 18 rods with 7m spacing: F ≈ 1.2
- R_multiple = 27.1/18 × 1.2
- R_multiple = 1.81 Ω
7. Overall System Resistance:
Parallel combination of rods and wire:
R_total = (R_multiple × R_wire)/(R_multiple + R_wire)
- R_total = (1.81 × 1.23)/(1.81 + 1.23)
- R_total = 2.23/3.04
- R_total = 0.73 Ω
Summary of Results:
| Parameter | Value |
|---|
| Single rod resistance | 27.1 Ω |
| Wire resistance | 1.23 Ω |
| Multiple rod resistance | 1.81 Ω |
| Overall system resistance | 0.73 Ω |
| Rod spacing | 7 meters |
| Number of rods | 18 rods |
| Wire size | 70 sq.mm copper |
Verification:
Total equipment resistance to be grounded:
- Lightning equipment: 0.5 Ω
- Power equipment: 2.0 Ω
- Combined parallel: (0.5 × 2.0)/(0.5 + 2.0) = 0.4 Ω
Final system resistance: 0.73 + 0.4 = 1.13 Ω
This meets typical industrial grounding requirements (usually < 5 Ω for most applications).