Robotics (&/or Automation) Technician cheat sheet.

From a Chatbot Arena battleThe same person sent this prompt to two anonymous models at once. Compare it with Geminigemini-2.5-flash-lite-preview-06-17-thinking’s answer.
  1. User

    Robotics (&/or Automation) Technician cheat sheet.

  2. Claude Assistant

    🔧 ROBOTICS & AUTOMATION TECHNICIAN QUICK REFERENCE 🔧

    EMERGENCY RESPONSE

    1. HIT E-STOP → 2. ASSESS DANGER → 3. LOTO IF NEEDED → 4. NOTIFY SUPERVISOR
    

    MULTIMETER QUICK CHECKS

    TestExpected ReadingBad Reading
    24VDC Sensor Power22-26 VDC<20V or 0V
    PNP Sensor Signal~24V when ON, 0V when OFFStuck at one value
    NPN Sensor Signal0V when ON, ~24V when OFFStuck at one value
    Motor Winding0.5-50Ω (matched phases)∞ (open) or 0Ω (short)
    Fuse Continuity0-1Ω∞ (blown)

    ROBOT FAULT CODES (Common)

    Code TypeMeaningQuick Fix
    SRVO-xxxServo faultCheck motor connections, encoder feedback
    MOTN-xxxMotion faultReduce speed, check payload, verify TCP
    COLL-xxxCollision detectedClear path, reduce sensitivity if needed
    INTP-xxxPosition errorRe-teach points, check mastering
    SYST-xxxSystem/MemoryReboot controller, check battery voltage

    PLC STATUS LIGHTS

    LEDColorMeaning
    RUNGreenProgram executing normally
    RUNFlashing GreenProgram in test/debug mode
    FAULTRedMajor fault - check fault table
    COMMGreenNetwork communication OK
    COMMFlashing YellowData transfer active
    I/OGreen per pointInput/Output is ON

    PNEUMATIC TROUBLESHOOTING

    No Movement → Check Pressure → Check Solenoid → Check Flow Control → Check Cylinder
    

    Quick Fixes:

    • Slow Movement: Open flow control valves
    • Jerky Movement: Add flow controls or check for air in lines
    • Won't Extend/Retract: Manual override solenoid, check for jams
    • Leaking: Replace seals or fittings

    Standard Pressures: 80-100 PSI (5.5-7 bar)


    ROBOT TEACHING SHORTCUTS

    BrandHome PositionJog Mode ToggleSpeed Override
    FANUCSHIFT + RESETCOORD key% buttons
    ABBHome → Motors OnJoystick modeSpeed bar
    KUKAHOME + StartCoordinate menu+/- keys
    YaskawaROBOT → HOME POSCOORD buttonSPEED HIGH/LOW

    WIRING COLOR CODES

    AC Power (US)

    • Black = L1 (Hot)
    • Red = L2 (Hot)
    • Blue = L3 (Hot)
    • White = Neutral
    • Green = Ground

    DC Control

    • Red = +24VDC
    • Black/Blue = 0VDC/Common
    • Other colors = Signals

    Sensor Standard

    • Brown = +V
    • Blue = 0V
    • Black = Signal
    • White = NO/NC (if present)

    NETWORK TROUBLESHOOTING

    Quick Checks:
    □ Link lights ON?
    □ Correct IP range?
    □ Ping successful?
    □ Duplicate IP?
    □ Cable good? (test with known good cable)
    

    Common IP Ranges:

    • 192.168.1.xxx (Most common)
    • 192.168.0.xxx
    • 10.0.0.xxx
    • 172.16.0.xxx

    VISION SYSTEM BASICS

    Poor Recognition?

    1. Clean lens/light
    2. Check exposure settings
    3. Verify lighting angle
    4. Re-train if needed
    5. Check focus

    Lighting Types:

    • Ring Light: Even illumination
    • Backlight: Silhouette/edge detection
    • Spot Light: Highlight features
    • Diffuse Dome: Eliminate shadows

    SAFETY CIRCUIT CHAIN

    E-Stop → Safety Relay → Door Switches → Light Curtain → Robot Enable
             ↓ Any Break = System Stop
    

    Reset Sequence:

    1. Clear the hazard
    2. Reset E-stops (turn and pull)
    3. Reset safety relay
    4. Reset robot controller
    5. Resume operation

    SERVO DRIVE LEDS

    PatternMeaning
    Solid GreenNormal operation
    Flashing RedFault (check display)
    YellowWarning/Standby
    Red + BeepCritical fault
    No LEDsNo power/blown fuse

    MECHANICAL CHECKS

    Daily Visual:

    • Oil leaks under robot
    • Unusual noises
    • Cable wear/damage
    • Loose bolts
    • EOAT secure

    Weekly:

    • Grease levels
    • Belt tension
    • Coupling alignment
    • Air filter condition

    COMMON MATH

    Cylinder Force:

    • Force (lbs) = Pressure (PSI) × Area (in²)
    • Area = π × (Diameter/2)²

    Gear Ratio:

    • Output Speed = Input Speed ÷ Gear Ratio

    Ohm's Law:

    • V = I × R
    • P = V × I

    BACKUP BATTERY VOLTAGES

    ComponentNormalReplace at
    Robot Controller3.6V<3.0V
    Absolute Encoder3.6V<3.2V
    PLC Memory3.0V<2.5V

    ⚠️ ALWAYS backup programs before battery replacement!


    TOOL CENTER POINT (TCP)

    Setting TCP:

    1. Touch reference point with tool tip from 4+ angles
    2. Robot calculates center point
    3. Verify with test moves
    4. Save TCP data

    Lost TCP Signs:

    • Path deviates from taught
    • Rotation not around tool tip
    • Inconsistent pick/place

    QUICK TERMINAL COMMANDS

    Windows CMD:

    ping 192.168.1.10        (Test connection)
    ipconfig /all           (Show network config)
    arp -a                  (Show IP/MAC table)
    

    Communication Test:

    • Robot→PLC: Check handshake bits
    • PLC→Robot: Monitor start signals
    • Lost Comms: Check heartbeat/watchdog

    PM SCHEDULE REMINDERS

    IntervalTask
    DailyClean sensors, check pressure
    WeeklyInspect cables, test E-stops
    MonthlyCheck filters, backup programs
    QuarterlyCalibrate, grease joints
    AnnuallyReplace batteries, major service

    📱 KEEP HANDY:

    • Manufacturer tech support numbers
    • System passwords (secured)
    • Backup location/procedure
    • Spare parts inventory
    • Last PM dates

    Remember: When in doubt, LOTO and call for help! Safety > Production