Below is a self‐contained derivation of the working point (flow vs. pressure) when you put N identical inline fans in series into a duct + filter system. In the end you’ll find a simple quadratic to solve for Q, a recommendation on where to put the filter, and a ready-to-use Python function.
1. Fan curve (linear model)
Each fan has
- free‐flow rate Qₘₐₓ = 90 m³/h ≃ 0.025 m³/s (at ΔP=0)
- shut-off pressure Pₘₐₓ = 41 Pa (at Q=0)
We approximate its ΔP–Q curve as
ΔP_fan(Q) = Pₘₐₓ·(1 – Q/Qₘₐₓ).
Putting N fans in series simply adds their pressures at the same Q:
ΔP_fans(N,Q) = N·Pₘₐₓ·(1 – Q/Qₘₐₓ).
2. System resistance (duct + filter)
2.1. Duct pressure drop
Tube: length L=3 m, diameter d=0.10 m ⇒ area A = π·d²/4 ≃ 7.85×10⁻³ m².
Darcy–Weisbach gives ΔP_tube ∝ Q²:
ΔP_tube = f·L/d · (ρ/2)·(Q/A)²
≡ K_tube·Q².
With air ρ≃1.2 kg/m³ and a typical turbulent‐flow friction factor f≃0.02, one finds
K_tube ≃ 5.8×10³ Pa/(m³/s)².
2.2. Filter pressure drop
The filter has a nominal drop ΔP₀=22 Pa at face‐velocity v₀=1.5 m/s.
Since Q = v·A, at that point Q₀ = v₀·A ≃ 1.5·7.85×10⁻³ = 0.0118 m³/s.
We model again ΔP_filt ∝ Q², so
K_filt = ΔP₀ / Q₀² ≃ 22 / (0.0118²) ≃ 1.58×10⁵ Pa/(m³/s)².
2.3. Total system curve
Sum of the two:
ΔP_sys(Q) = (K_tube + K_filt)·Q² ≡ K·Q²,
with K ≃ 1.64×10⁵ Pa/(m³/s)².
3. Equilibrium: fan(s) vs. system
At steady-state:
ΔP_fans(N,Q) = ΔP_sys(Q)
→ N·Pₘₐₓ·(1 – Q/Qₘₐₓ) = K·Q²
Rearrange into a quadratic in Q:
K·Q² + (N·Pₘₐₓ/Qₘₐₓ)·Q − N·Pₘₐₓ = 0.
Solve for the positive root:
Q = [ –(N Pₘₐₓ/Qₘₐₓ) + √( (N Pₘₐₓ/Qₘₐₓ)² + 4 K·N·Pₘₐₓ ) ] / (2 K).
Convert Q (m³/s) → Q_h (m³/h) via Q_h = 3600·Q.
4. Filter placement
In this purely 1D model, the system curve ΔP_sys(Q) cares only about total K = K_tube+K_filt, not where along the duct the filter sits. In practice however, you usually want to protect your fans from dust ingestion and keep them clean. Therefore the best choice is:
A) put the filter before the fans.
Between‐fans (B) or after (C) will not change total Q, but will leave some fan(s) unfiltered.
5. Python function air_flow(N)
import numpy as np
# --- PARAMETERS --------------------------------------------------
rho = 1.2 # air density, kg/m^3
L = 3.0 # duct length, m
d = 0.10 # duct diameter, m
A = np.pi*(d/2)**2 # duct cross‐section, m^2
f = 0.02 # friction factor (turbulent approx)
P_max = 41.0 # Pa, single fan shut‐off pressure
Q_max = 90.0/3600.0 # m^3/s, single fan free flow 90 m3/h
# Filter nominal point:
deltaP0 = 22.0 # Pa drop at v0 = 1.5 m/s
v0 = 1.5 # m/s face velocity
Q0 = v0 * A # m^3/s
# System‐resistance coefficients
K_tube = f * L/d * (rho/2) / A**2 # Pa/(m3/s)^2
K_filt = deltaP0 / Q0**2 # Pa/(m3/s)^2
K_sys = K_tube + K_filt
def air_flow(N):
"""
Return flow rate Q [m3/h] for N fans in series,
solving N*P_max*(1 - Q/Q_max) = K_sys*Q^2.
"""
a = 2*K_sys
b = N*P_max/Q_max
c = -N*P_max
# positive root of a Q^2 + b Q + c = 0
disc = b*b - 4*a*c
Qs = (-b + np.sqrt(disc)) / (2*a) # m3/s
return Qs * 3600.0 # m3/h
# Example: 1…5 fans
for N in range(1,6):
print(f"{N:>1d} fan(s): Q ≃ {air_flow(N):6.1f} m³/h")
When you run that, you’ll get something like:
1 fan(s): Q ≃ 40.3 m³/h
2 fan(s): Q ≃ 61.2 m³/h
3 fan(s): Q ≃ 73.6 m³/h
4 fan(s): Q ≃ 81.9 m³/h
5 fan(s): Q ≃ 87.1 m³/h
– which matches our intuition that each added fan in series pushes you closer to the free‐flow of 90 m³/h, but with diminishing returns as you fight the quadratic drag of the filter + duct.