  1. User

    I'm doing some heat flow equations

    I have the 'design duty' of heat sources and heat absorbers, and I need to find a multivariable 'conversion' value that looks at both temperature and flow so I can calculate the heat flow in this equipment based on the underlying instrument readings

    for example, 'Water Heater' (hot water flowing through tubes in a larger vessel to heat that vessel filled with oily water)

    Q = 0.35 MW Temp In = 190 degC Mass Flow = 5781 kg/h Temp Out = 140 degC

  2. Assistant

    Okay, you're looking for the value that relates the heat flow (Q) to the mass flow (m˙\dot{m}) and the temperature difference (ΔT\Delta T). This relationship is governed by the basic heat transfer equation for a fluid:

    Q=m˙×Cp×ΔTQ = \dot{m} \times C_p \times \Delta T

    Where:

    • QQ is the heat flow rate (e.g., in kW or MW)
    • m˙\dot{m} is the mass flow rate (e.g., in kg/s or kg/h)
    • CpC_p is the specific heat capacity of the fluid (e.g., in kJ/(kg·°C) or kJ/(kg·K))
    • ΔT\Delta T is the temperature difference across the equipment (Tout−TinT_{out} - T_{in} if the fluid is heated, or Tin−ToutT_{in} - T_{out} if the fluid is cooled, as in your example).

    The "multivariable conversion value that looks at both temperature and flow" is essentially related to the properties of the fluid you are heating or cooling, specifically its specific heat capacity (CpC_p).

    If you know CpC_p for your fluid, you can calculate Q for any given m˙\dot{m} and ΔT\Delta T.

    However, your data point lets you calculate the effective CpC_p for your fluid under these specific conditions, or alternatively, calculate the combined term (m˙×Cp)(\dot{m} \times C_p) for your design flow rate.

    Let's calculate CpC_p from your example data:

    1. Identify the variables:

      • Q=0.35Q = 0.35 MW
      • m˙=5781\dot{m} = 5781 kg/h
      • Tin=190T_{in} = 190 °C
      • Tout=140T_{out} = 140 °C
    2. Calculate the temperature difference (ΔT\Delta T): Since the water is cooling down (190°C to 140°C), ΔT=Tin−Tout\Delta T = T_{in} - T_{out}. ΔT=190\Delta T = 190 °C - 140 °C = 50 °C. (Note: A difference in °C is the same as a difference in K, so you can use 50 K in calculations involving CpC_p).

    3. Ensure consistent units: QQ is in MW (MegaWatts), which is MJ/s or kJ/ms. CpC_p is typically in kJ/(kg·°C) or kJ/(kg·K). m˙\dot{m} is in kg/h. Let's convert everything to be compatible with kJ, kg, seconds, and °C or K.

      • Q=0.35Q = 0.35 MW = 0.35×10000.35 \times 1000 kW = 350350 kW = 350350 kJ/s
      • m˙=5781\dot{m} = 5781 kg/h. To convert to kg/s, divide by the number of seconds in an hour (3600): m˙=5781 kg3600 s≈1.6058\dot{m} = \frac{5781 \text{ kg}}{3600 \text{ s}} \approx 1.6058 kg/s
    4. Rearrange the equation to solve for CpC_p: Q=m˙×Cp×ΔTQ = \dot{m} \times C_p \times \Delta T Cp=Qm˙×ΔTC_p = \frac{Q}{\dot{m} \times \Delta T}

    5. Plug in the values and calculate: Cp=350 kJ/s(1.6058 kg/s)×(50 °C)C_p = \frac{350 \text{ kJ/s}}{(1.6058 \text{ kg/s}) \times (50 \text{ °C})} Cp=350 kJ/s80.29 kg⋅°C/sC_p = \frac{350 \text{ kJ/s}}{80.29 \text{ kg·°C/s}} Cp≈4.359kJkg⋅°CC_p \approx 4.359 \frac{\text{kJ}}{\text{kg} \cdot \text{°C}} (or kJ/(kg·K))

    Interpretation:

    The "conversion value" you can derive from this data is the specific heat capacity (CpC_p) of the fluid, which is approximately 4.359 kJ/(kg·°C) under the operating conditions described.

    How to use this value for future calculations based on instrument readings:

    Assuming the specific heat capacity (CpC_p) of your fluid remains relatively constant over your expected operating range of temperatures and pressures, you can use this calculated CpC_p value to predict the heat flow (Q) from future instrument readings of mass flow (m˙\dot{m}) and temperatures (Tin,ToutT_{in}, T_{out}):

    Qactual=m˙actual×Cp×(Tin,actual−Tout,actual)Q_{actual} = \dot{m}_{actual} \times C_p \times (T_{in, actual} - T_{out, actual})

    Where:

    • QactualQ_{actual} will be in kW (or kJ/s) if m˙actual\dot{m}_{actual} is in kg/s and CpC_p is in kJ/(kg·°C).
    • m˙actual\dot{m}_{actual} is your instantaneous mass flow reading (remember to convert kg/h to kg/s if needed).
    • Tin,actualT_{in, actual} and Tout,actualT_{out, actual} are your instantaneous temperature readings.

    Important Considerations:

    1. CpC_p is not perfectly constant: The specific heat capacity of a fluid (like water) varies slightly with temperature and pressure. The value you calculated (4.359 kJ/(kg·°C)) is the effective average CpC_p over the temperature range of 190°C to 140°C and the pressure conditions present in your equipment. If your future operating temperatures are significantly different, the actual CpC_p might vary, introducing some error into your Q calculation.
    2. Fluid Composition: If the "oily water" mixture's composition changes, the CpC_p of the fluid will change. The calculated CpC_p is for the fluid at the time of the design duty.
    3. Phase Changes: The equation Q=m˙×Cp×ΔTQ = \dot{m} \times C_p \times \Delta T applies when the fluid is in a single phase (liquid or gas). If the fluid undergoes a phase change (like boiling or condensing), latent heat is involved, and this simple equation isn't sufficient. Your temperature range (190°C to 140°C) suggests the water is under pressure to remain liquid above 100°C.

    In summary, calculate the specific heat capacity (CpC_p) from your design data (4.359 kJ/(kg·°C)). This CpC_p value acts as your primary "conversion value" that links flow and temperature difference to heat flow. Use the formula Q=m˙×Cp×ΔTQ = \dot{m} \times C_p \times \Delta T with actual readings to estimate heat flow.