Okay, let's perform a mass balance on the pulverized coal-fired boiler based on the given inputs and assumptions.
First, we need to calculate the mass flow rates of each component entering the boiler.
1. Input Mass Flow Rates:
-
Coal: 114.8 kg/s (given)
-
Air: To calculate the air flow rate, we need to determine the stoichiometric (theoretical minimum) amount of oxygen required for complete combustion and then add the 30% excess.
-
Coal Composition (Mass Flow Rates):
- Sulfur (S): 114.8 kg/s * 0.021 = 2.4108 kg/s
- Ash: 114.8 kg/s * 0.08 = 9.184 kg/s
- Combustible (assume Carbon, C, as per problem statement): 114.8 kg/s * (1 - 0.021 - 0.08) = 114.8 kg/s * 0.899 = 103.2052 kg/s
-
Stoichiometric Oxygen (O2) Required:
- For Sulfur: S + O2 -> SO2
- Molar masses: S=32 g/mol, O2=32 g/mol. Mass ratio O2/S = 32/32 = 1
- O2 needed for S: 2.4108 kg/s * 1 = 2.4108 kg/s
- For Carbon: C + O2 -> CO2
- Molar masses: C=12 g/mol, O2=32 g/mol. Mass ratio O2/C = 32/12 ≈ 2.6667
- O2 needed for C: 103.2052 kg/s * (32/12) = 275.2139 kg/s
- Total Stoichiometric O2: 2.4108 + 275.2139 = 277.6247 kg/s
-
Actual Oxygen (O2) Supplied:
- Excess O2 = 30% of Stoichiometric O2 = 0.30 * 277.6247 kg/s = 83.2874 kg/s
- Total O2 Supplied = Stoichiometric O2 + Excess O2 = 277.6247 + 83.2874 = 360.9121 kg/s
-
Air Supplied:
- Assume standard dry air composition by mass: approximately 23.14% O2 and 76.86% N2.
- Total Air Mass = Total O2 Supplied / Mass fraction of O2 in air
- Total Air = 360.9121 kg/s / 0.2314 = 1560.55 kg/s
- Nitrogen (N2) Supplied = Total Air * Mass fraction of N2 in air
- N2 Supplied = 1560.55 kg/s * 0.7686 = 1199.64 kg/s
-
Check: O2 + N2 = 360.9121 + 1199.64 = 1560.55 kg/s. Matches total air.
-
Total Mass Entering Boiler:
- Total Input = Mass of Coal + Mass of Air
- Total Input = 114.8 kg/s + 1560.55 kg/s = 1675.35 kg/s
2. Output Mass Flow Rates:
The output consists of combustion products in the stack gas (SO2, CO2), unreacted components from air in the stack gas (N2, O2), fly ash in the stack gas, and bottom ash.
3. Mass Balance Verification:
- Total Mass Entering: 1675.35 kg/s
- Total Mass Leaving: 1675.3518 kg/s
The total mass entering the boiler (1675.35 kg/s) is equal to the total mass leaving the boiler (1675.3518 kg/s) within the precision of the calculations and assumed air composition percentages.
Summary of Results:
Rounding slightly for presentation in the summary but using the more precise numbers for the totals confirms the mass balance.