For a redundant 24VDC NEC Class 2 power architecture with dual 120VAC UPS sources, here's the optimal design:
Power Architecture
Primary Configuration: Dual independent 24VDC power supplies with diode ORing for automatic failover. Each supply connects to a separate 120VAC UPS circuit to eliminate single points of failure.
Supply Selection: Use DIN rail mount switching power supplies rated for 24VDC output with 120VAC input. Size each supply for 100% of the total load to ensure full redundancy. Select supplies with built-in current limiting and short circuit protection to maintain NEC Class 2 compliance.
Key Components BOM
Power Supplies: Two identical 24VDC switching supplies (Phoenix Contact QUINT4-PS/1AC/24DC or equivalent), sized per load requirements with 20% derating factor.
Diode ORing Module: Redundancy module with Schottky diodes (Phoenix Contact QUINT-DIODE or similar) to prevent backfeed between supplies and provide seamless failover.
Circuit Protection: Individual 5A max circuit breakers or fuses for each 24VDC output circuit to maintain Class 2 current limitations. Use supplementary protectors rated for 24VDC.
Input Protection: 15A circuit breakers for each 120VAC input, coordinated with upstream UPS protection.
Terminal Blocks: DIN rail mount terminals with appropriate current ratings, separate blocks for AC input, DC output, and grounding.
Grounding Design
Equipment Grounding: Bond all metallic enclosure components and DIN rail to the main equipment grounding conductor from the panel's grounding bus. Use #12 AWG minimum copper conductor.
Isolated Ground Architecture: Maintain galvanic isolation between 120VAC and 24VDC systems. The 24VDC negative can be left floating or referenced to equipment ground through a single point connection if required by connected equipment.
Grounding Bus: Install dedicated grounding bus bar in panel, connected to building ground system. All equipment grounds terminate here, with star-point grounding topology to minimize ground loops.
This architecture provides true redundancy while maintaining NEC Class 2 compliance through proper current limiting and circuit protection at both the supply and distribution levels.