As mentioned, the sensitivity test was successfully performed during the HV test:
“The sensitivity test has been successfully carried out during the HV test, so it may not be necessary to install the PDC as initially planned.”
Therefore, it may also not be necessary to install the additional sensor that was previously "forgotten".
However, the key point is under what conditions this sensitivity test was performed. It is essential that the test is conducted using the signal level defined during STEP 1 of the sensitivity calibration, as referenced in the attached report R47.00882-PE.
According to this document, for the F35-41 GIS, the defined signal level is 5V. This 5V value is the reference for both the F35-41 and F35-41g GIS units. This report is typically attached to the tender documents or handed over to the customer during the project phase. Without this report, a proper HV test including UHF PD measurement is practically impossible.
If a 5V signal is clearly observed between two sensors, one can conclude that the distance (or coverage) between those sensors is sufficient. In such a case, one sensor may potentially be omitted.
However, your request lacks several key details:
- No SLD (Single Line Diagram) or sensor layout is provided,
- No information about signal amplitudes,
- No description of the test conditions,
- No information about the type of calibrator used (we use the PDx CAL2B).
Frankly speaking, these missing details make it difficult to provide a fully informed technical recommendation.
The guidelines provided by SEH are designed to ensure that any signals generated by actual defects are detectable. UHF sensors enable monitoring and even on-site testing without the need for coupling capacitors.
In my personal opinion, UHF sensors should either be installed correctly—ensuring they can reliably detect PD—or not installed at all. Installing too many sensors can be counterproductive, as it may lead to the detection of irrelevant signals or increased noise levels, potentially resulting in false positives during continuous monitoring. This, in turn, can increase uncertainty and reduce customer confidence in our products.