To solve this problem, we'll determine the fundamental output voltage of the inverter, refer it to the secondary side of the transformer, and use power equations in an AC circuit to find the power angle and reactive power.
1. Calculate the Inverter Output Voltage Fundamental Component (Before Transformer):
Given:
- DC voltage, ( V_{\text{dc}} = 96,\text{V} )
- Modulation index, ( m = 0.8 )
For a single-phase full-bridge inverter using bipolar SPWM, the fundamental component of the output voltage (peak value) is:
[
V_{\text{1,peak}} = m \cdot V_{\text{dc}}
]
The RMS value is:
[
V_{\text{1,RMS}} = \frac{V_{\text{1,peak}}}{\sqrt{2}} = \frac{m \cdot V_{\text{dc}}}{\sqrt{2}}
]
Substituting the values:
[
V_{\text{1,RMS}} = \frac{0.8 \times 96,\text{V}}{\sqrt{2}} = 54.35,\text{V}
]
2. Refer the Inverter Voltage to the Secondary Side of the Transformer:
Transformer voltage ratio is ( 75,\text{V} / 375,\text{V} ), so the voltage steps up by a factor of 5:
[
V_{\text{inv,RMS}} = V_{\text{1,RMS}} \times 5 = 54.35,\text{V} \times 5 = 271.73,\text{V}
]
3. Calculate the Power Angle (( \delta )):
Given the grid voltage ( V_{\text{grid}} = 230,\text{V} ), the reactance ( X = 2,\Omega ), and the real power ( P = 7,\text{kW} ).
The power transferred ( P ) is given by:
[
P = \frac{V_{\text{inv,RMS}} \cdot V_{\text{grid}}}{X} \cdot \sin(\delta)
]
Plugging in the known values:
[
7000,\text{W} = \frac{271.73,\text{V} \times 230,\text{V}}{2,\Omega} \cdot \sin(\delta)
]
Calculate the numerator:
[
271.73,\text{V} \times 230,\text{V} = 62,498.46,\text{V}^2
]
Then:
[
7000 = \frac{62,498.46}{2} \cdot \sin(\delta) \
7000 = 31,249.23 \cdot \sin(\delta)
]
Solve for ( \sin(\delta) ):
[
\sin(\delta) = \frac{7000}{31,249.23} \approx 0.224
]
Thus:
[
\delta = \arcsin(0.224) \approx 12.94^\circ
]
4. Calculate the Reactive Power (( Q )) Supplied by the Inverter:
Reactive power ( Q ) is given by:
[
Q = \frac{V_{\text{inv,RMS}}^2 - V_{\text{inv,RMS}} \cdot V_{\text{grid}} \cdot \cos(\delta)}{X}
]
First, calculate ( V_{\text{inv,RMS}}^2 ):
[
V_{\text{inv,RMS}}^2 = (271.73,\text{V})^2 = 73,838,\text{V}^2
]
Next, calculate ( V_{\text{inv,RMS}} \cdot V_{\text{grid}} \cdot \cos(\delta) ):
[
V_{\text{inv,RMS}} \cdot V_{\text{grid}} \cdot \cos(12.94^\circ) = 271.73,\text{V} \times 230,\text{V} \times 0.976 \approx 60,975.51,\text{V}^2
]
Now compute ( Q ):
[
Q = \frac{73,838 - 60,975.51}{2} = \frac{12,862.49}{2} = 6,431.25,\text{VAR}
]
So, the inverter supplies approximately ( 6.43,\text{kVAR} ) of reactive power.
Answer:
An explicit answer:
• Power angle δ ≈ 12.94 degrees; Reactive power supplied ≈ 6431 VAR (about 6.43 kVAR)