To determine the conditions under which condensation occurs on the inner surface of the wall and how to prevent it by adding insulation, we'll analyze the heat transfer through the wall system. Here's a step-by-step solution to both parts of the problem.
Given Data:
- Wall Properties:
- Thickness (( L_{\text{wall}} )) = 10 cm = 0.1 m
- Thermal conductivity (( k_{\text{wall}} )) = 0.47 W/m·K
- Polystyrene Insulation:
- Thermal conductivity (( k_{\text{insul}} )) = 0.035 W/m·K
- Convection Heat Transfer Coefficients:
- External surface (( h_e )) = 23.3 W/m²·K
- Internal surface (( h_i )) = 11.6 W/m²·K
- Internal Environment:
- Temperature (( T_i )) = 15°C
- Relative Humidity (( RH_i )) = 80%
- Condition for Condensation:
- Dew Point (( T_d )) ≈ 11°C (approximate calculation for 15°C and 80% RH)
Part 1: Determining the External Temperature ( T_e ) Causing Condensation
Objective: Find the external temperature ( T_e ) at which the inner surface temperature (( T_s )) drops to the dew point (( T_d = 11°C )), causing condensation.
Approach:
-
Calculate Thermal Resistances:
- Convective resistance on the internal surface:
[ R_i = \frac{1}{h_i} = \frac{1}{11.6} \approx 0.0862 , \text{m²·K/W} ]
- Conductive resistance through the wall:
[ R_{\text{wall}} = \frac{L_{\text{wall}}}{k_{\text{wall}}} = \frac{0.1}{0.47} \approx 0.2128 , \text{m²·K/W} ]
- Convective resistance on the external surface:
[ R_e = \frac{1}{h_e} = \frac{1}{23.3} \approx 0.0429 , \text{m²·K/W} ]
- Total Thermal Resistance:
[ R_{\text{total}} = R_i + R_{\text{wall}} + R_e \approx 0.3419 , \text{m²·K/W} ]
-
Heat Transfer Rate (( q )):
[ q = \frac{T_i - T_e}{R_{\text{total}}} ]
-
Condition for Condensation:
[ T_s = T_i - q \cdot R_i \geq T_d ]
[ 15 - q \cdot 0.0862 \geq 11 ]
[ q \leq \frac{4}{0.0862} \approx 46.43 , \text{W/m²} ]
-
Solving for ( T_e ):
[ \frac{15 - T_e}{0.3419} \leq 46.43 ]
[ 15 - T_e \leq 15.83 ]
[ T_e \geq -0.83°C ]
Conclusion: Condensation on the inner surface occurs when the external temperature ( T_e ) drops to approximately -0.83°C.
Part 2: Determining the Minimum Thickness of Polystyrene to Prevent Condensation at ( T_e = -10°C )
Objective: Find the minimum thickness (( L_{\text{insul}} )) of polystyrene insulation required to prevent the inner surface temperature from dropping below the dew point (( T_d = 11°C )) when the external temperature is -10°C.
Approach:
-
Calculate Existing Thermal Resistances:
[ R_i = \frac{1}{11.6} \approx 0.0862 , \text{m²·K/W} ]
[ R_{\text{wall}} = \frac{0.1}{0.47} \approx 0.2128 , \text{m²·K/W} ]
[ R_e = \frac{1}{23.3} \approx 0.0429 , \text{m²·K/W} ]
[ R_{\text{existing}} = R_i + R_{\text{wall}} + R_e \approx 0.3419 , \text{m²·K/W} ]
-
Total Thermal Resistance Required to Prevent Condensation:
[ T_s = T_i - q \cdot R_i \geq 11°C ]
[ 15 - q \cdot 0.0862 \geq 11 ]
[ q \leq 46.43 , \text{W/m²} ]
Using ( q = \frac{T_i - T_e}{R_{\text{total}}} ):
[ \frac{15 - (-10)}{R_{\text{total}}} \leq 46.43 ]
[ \frac{25}{R_{\text{total}}} \leq 46.43 ]
[ R_{\text{total}} \geq \frac{25}{46.43} \approx 0.538 , \text{m²·K/W} ]
-
Additional Resistance Needed from Insulation:
[ R_{\text{insul}} = R_{\text{total}} - R_{\text{existing}} \geq 0.538 - 0.3419 = 0.1961 , \text{m²·K/W} ]
-
Calculating Minimum Polystyrene Thickness (( L_{\text{insul}} )):
[ R_{\text{insul}} = \frac{L_{\text{insul}}}{k_{\text{insul}}} ]
[ 0.1961 = \frac{L_{\text{insul}}}{0.035} ]
[ L_{\text{insul}} = 0.1961 \times 0.035 \approx 0.006864 , \text{m} ]
[ L_{\text{insul}} \approx 6.86 , \text{mm} ]
Conclusion: A minimum polystyrene insulation thickness of approximately 7 mm is required to prevent condensation on the inner surface when the external temperature is -10°C.
Final Summary:
- Condensation occurs on the inner surface when the external temperature drops to approximately -0.83°C.
- To prevent condensation at an external temperature of -10°C, a minimum of 7 mm of polystyrene insulation should be added to the existing wall.
Visualization:
[image: Thermal Resistance Diagram] open
Figure: Thermal resistances from internal air, through the wall and insulation, to external air.