can you make this professional? Bill,
I checked all of the ORs with the anemometer and all were positive at ~150 ft/min.
I left the doors open in the ORs for well over two minutes to try to trigger the alarm in the ORs but was unsuccessful. When I measured the airflow with the doors open it was still positive at ~50 ft/min which is why I think the alarm did not trigger.
The only OR that had an exterior door with negative pressure was OR 6. It is negative pressure from the hall to the control station but the second set of doors that go into the OR were positive to the control station at ~ 150 ft/min.
Then I measured the hall to the PACU and it is also positive.
Matt B.
- Assistant
Dear Bill,
Upon conducting an assessment of the operating rooms (ORs) using an anemometer, I found that all ORs showed positive airflow at approximately 150 ft/min.
Despite leaving the doors in the ORs open for an extended period exceeding two minutes, I was unable to trigger the alarm, as the airflow remained positive at around 50 ft/min. This may explain why the alarm did not activate.
Among the ORs, only OR 6 exhibited negative pressure from the exterior hall to the control station. However, the second set of doors leading into the OR showed positive airflow towards the control station at approximately 150 ft/min.
Furthermore, my measurements indicated that the airflow from the hall to the Post-Anesthesia Care Unit (PACU) also displayed positive pressure.
Regards,
Matt B.